E16 Systems for High Safety Speed Monitoring, all with Triple Modular Redundancy.
A choice of versions to meet various demands. Compliant with SIL3 / IEC 61508 and/or API 670.

E16 - the core
|
Outstanding Characteristics
-
At no point does safety depend on only a single element, and the machine cannot be tripped by an individual error.
Thereby enhanced safety and protection against a false trip. Reduces costs and increases machine availability.
-
Each channel provides an extra input accepting an external signal for an alternative condition (temperature, pressure, flame), for possible inclusion into the voted trip.
-
Sensor monitoring, channel comparison, and plausibility check for the measurements detect a failure in its early stage, releasing a separate warning.
Input frequency divider balances irregularities of the target profile. Programmable 001 through 256.
|
|
-
The safety trip relay contacts of the 3 Monitors are ready hard wired on the back plane of the system to terminals, providing 2 isolated breaking trip circuits with a 2of3 voting, or separately from each monitor, as option.
Optional Test Module
The three channels can be augmented by an independent Test Generator Module. This enables under load response checks by sequentially applying its speed simulating frequency signal to each channel. This can be carried out manually by push buttons at the system, or optionally as an automatic test routine following a programmed test cycle, under full operation of the turbine. Each channel's reaction to the test is observed, and a failure signal released if the response is not as expected.
More functions as option To meet further demands, additional functions are available, to each of the 3 channels (alarms then with an additional 2of3 voter on request):
|
|
E16 - a very flexible series of systems. Available with any required safety characteristics and additional functions.
E16 groups meet different safety requirements - their Nomenclature and Compliance to Standards
By two groups of versions the E16 provides optimum adaptation to the safety grade and comfort as appropriate for the application. Both groups E16x3 and E16x4 have the 3-channel architecture with its safety in trip release and protection against erratic tripping. All with the functional safety and specific advantages as described for the monitors. Both groups offer the same options regarding their mechanical design and data interface mode. Several additions are available for both groups: analog outputs, more speed alarms, forward/reverse detection, comparison with another drive, and acceleration monitor, all making use of the safeguarded channel inputs.
|
-
The E16X3 group is designed to comply to the highest safety level, and is approved to SIL3 according to IEC 61508, with intrinsic double self-check facility. All versions within this include a Test Generator Module. If equipped to perform the periodic test routine it exempts the user from the otherwise required periodic checks and the associated documentation, thereby saving service labour cost.
|
|
The E16X4 group covers applications not affording this high testing comfort. However, they provide the same safety degree complying to the API 670 Standard. Also in this group, a Test generator is available and recommended as option.
See the below nomenclature defining the core versions and additional functions
|
 |
|
General Specifications applying to all Systems Trip output of the system With the 2of3 voting incorporated in the system, the contacts of both safety relays on each monitor are hard wired by the system backplane to two separate and isolated breaking circuits. An optional version has the same safety NO contacts are separately wired to the output terminals.
The power handling facilities as listed for the individual monitor also apply to the system trip output. Power Supply Standard 3x24 v DC (18.. 33 v) separate per channel, common zero. An incorporated diodes network feeds modules not assigned to a specific channel. Power consumption (without additions) 3x 0.5 A.
Options 2x 115 v AC (100..130 v) or 2x230 V AC (200..253 v), feeding a common rail within the system. Power approx. 60 VA.
Insulation and Electric Protection grade I, voltage class I.
|
|
Mechanical design options
Ambient Conditions Temperature:
- in operation 0 ..+60 °C ( 30 ..105 °F),
- for storage -40 °C .. + 85 °C (-18...+ 30 °F).
Humidity:
- max 95 % (no condensation)
EMI and CE Compliance to Standards 89/336/EWG, EN 61000-6-2, -6-4.
|
 19- inch Design Version ( E )
|
E16 - the Safety Concept Permanently performed Intrinsic checks within the monitors for early failure detection
Any of these criteria can be included per program into a collective alarm, which is part of the monitor's trip conditions. The major criterion certainly is the excess of SP1, the overspeed alarm level.
Another one comes from outside the system. Each channel accepts a contact or electronic signal as a peripheral alarm condition, for instance from a temperature or pressure monitor, or a flame guard. The user decides per program which of these criteria the channel alarm comprises, in order to release the trip output. And, a similarly programmed selection further actuates a separate warning output of the monitor module.
|
|
The 2 of 3 voting principle
3 monitoring channels operate in parallel. Each encompasses in its monitoring module the entire function: sensor signal input, measurement, setpoint alarm, peripheral alarm. Its trip alarm or the collective alarm actuates the two monitor incorporated safety relays, each with two contact sets as output and one as response feedback.
The system trip however is not released before 2 of the 3 monitors enter their programmed trip condition. A discrepancy between the 3 monitors will be detected, but does not result in machine tripping.
With the 2of3 voting incorporated in the system, these outputs of the monitors are directly wired on the system backplane. Forming two isolated trip circuits, breaking to trip, if at least two monitors are in trip condition. Only one monitor in trip condition, for whatever reason, cannot release the trip output of the system. With separate channel trip outputs, the external 2of3 voting (by electric or hydraulic means) must achieve this. However, the E16 thus equipped, provides inputs expecting return signals from the peripheral actuators acknowledging their correct response.
|
A single channel in error cannot activate the trip,
nor can it release an erratic shutdown.
Safety never depends on merely one element or one signal
|
|

E16 - surface mount version
|

surface mount version - look on top
|
|
|
Details of the Monitor Modules Speed measuring principle Utilizing the advantageous principle of quartz controlled pulse distance evaluation, automatically extended over a minimum period of time (5 millisec). The ideal combination of fast response and steady measurements, as appropriate for turbine speed monitoring. Programmable relationship between turbine RPM and signal frequency (Hz), thereby all readings and presets in RPM terms. Accuracy ± 0,005 % ± 1 in the last of 5 digits. Speed setpoint alarms 3 programmable alarms on every monitor, each reacting within 15 millisec + 1 measuring period (see above). Setpoint SP1 is assigned to the overspeed trip alarm, programmable for setpoint and hysteresis bandwidth. Actuates the safety relays as the trip output of the monitor and participates in its failure signal (see below).
Setpoint SP2 is used for the intrinsic plausibility check: any measurement below this programmable level (during machine operation) registers an obvious function failure of the monitor (check to be disengaged for the turbine start up). Setpoint SP3 is freely available to set to any other speed level, programmable for its response characteristics, as its hysteresis bandwidth and position, its condition at setpoint excess or not-excess, and start-up state. Output as a NO- contact. The start-up signal throws SP2 and SP3 to a programmed condition. Following an external contact or pulse signal, the duration of its validity can be extended by program up to 999 s. The alarm released may be kept memorized for a later analysis. Trip output of the monitor Both safety relays on every monitor module drop to de-energized state under one of the following conditions:
- Overspeed = SP1 setpoint level exceeded, or
- collective intrinsic failure signal, or
- external trip condition signal.
Both safety relays provide 2 NO-contacts directly to the 2of3 wiring on the backplane or to separate terminals. A further contact is used internally by the system to signal correct monitor response to the (optional) test module. Power handling facility of the trip output contacts: Standard max 130 v AC/DC, max 2 a AC/DC, max 100 w. Overload protection must be provided externally. Collective intrinsic failure signal With programmable selection the monitor assembles these failure signals as its intrinsic collective failure signal acting as one of the trip release conditions (see above):
- sensor circuit failure as supply interrupt, short circuit, or signal lead inactivity (presumes a p/p output as with our A5S.. sensors),
- plausibility check by SP2 (see above) fails,
- sensor signal fails in pulse amount equality compared to both its neighbours.
The collective failure signal breakes a relay contact as an externally available alarm. Each of the above individual failure signals may be memorized or automatically cancelled by programmable selection, once its cause has been eliminated.
Sensor input The standard monitor input fits our recommended A5S.. or equivalent sensors. On/off level >7 / < 3 v, with 3k input impedance. Optional input for low level magnetic sensors, response 150/300 millivolts and low pass filter selection by program. Input circuit isolated, max signal 60 v, frequency 0...30 kHz. Sensor supply approx + 11 v, max 60 ma, short circuit protected. In the "test" condition, the monitor input is switched by the electronics to the test generator signal.
|
|
Display 5-digits led 8 mm height. In operation, speed by programmed unit, failures identified by listed code. During the programming phase, the display reads program steps and parameters. Conditions signalized by single LEDs. Data interface Output: measurements and alarms on demand. Input to configure the operational parameters (in addition to the front keys). Standard mode RS232, optional PROFIBUS. Connection to front socket Sub-D. Output repeating the sensor input Square wave pulses in same sequence as the input signal, not affected by switching of the monitor to test. Level approx. 22 volts under 1 k load. Output isolated and without a reaction to the monitor function. Analog outputs (option)
Up to 3 outputs with 20 ma into 500 ohms max load. Each individually programmable for low and high end of its span, with or without live zero. Programmable response to test condition, level at failure condition, rising or falling output with increasing speed.
Resolution 12 bit, linearity error < 1 %. Not available for monitors with PROFIBUS interface.
Details of the (optional) Test Generator Module Continuous testing provides a reliable knowledge of the system's reaction to danger and greatly increases the safety factor. Therefore an appropriate test routine is highly recommended, indispensable for the SIL3 safety level. The Test Generator Module provides the frequency signals simulating the speed signal to the monitor modules to check their response to different speeds. The Test Module reads the actual test frequency (in terms of RPM) on its display, and indicates which channel is currently under test. Frequency selection is available in several modes:
- manual tuning over the entire range by narrow steps,
- 4 pre-programmable frequency (speed) levels for automatic application during the course of a test procedure.
The tests may be carried out according to the following options:
- Manual selection of the channel to be tested, by push-button or external signal. The reaction being made apparent by its alarm LED and its monitor collective failure alarm,
- Automatic test procedure, performed in a regular and sequential manner. The monitor response is checked internally by auxiliary contacts of its safety relays, addressing the Test module. A separate system failure alarm is released if one response is not as expected. Further tests are stopped, to prevent of any erratic shut down of the machine.
Intrinsic Self Tests The Test Generator module controls the entire test procedures.
The version performing the automatic test routine as approved to SIL3 IEC 61508 has a multiple self test facility, monitoring the correct sequence and timing of all steps, and actuating its own system failure signal, if not as anticipated.
|
General Functional Diagram (red = optional)

Optional facilities in conjunction with the A, B, C inputs

|
Specifications of the Optional Facilities
|
|
Additional speed alarms
Options:
4, or 8, in addition to each channel A, B, C. Setpoints individually programmable over the entire range, also their response characteristics, the signal condition at power failure and during the starter phase.
|
| Alarm outputs
Options:
1 each separate SPNO relay contact with programmable alarm position. Additional 2of3 voting between channels A, B, C, as breaking circuit.
|
| Contacts Capacity:
Max. 130 Volts AC/ DC, 2 amps AC or DC, max. 100 W. Higher voltage capacity on request. Overload protection required for inductive type loads.
|
|
Response Time:
1 input signal period at setpoint + 15 milliseconds.
|
Analog outputs:
1, or 2, or 3 available as optional parts of the Core Monitor, in each channel A, B, C. Each isolated. Full scale 20 ma into max. 500 ohms load. High and low end of range, and live zero individually programmable. Resolution 12 bit (1. 4096). Linearity error < 0.1 % of full scale. Note: the analog output adds 2 milliseconds to the monitor reaction time.
|
Sense of Rotation Monitor
Addition to any channel A, B, C with special input to Sensor Series A5S30 ...33,
Optional as stand alone addition with own extra input.
|
| Contact Output:
2 isolated SPDT contacts reversing with motion signal, as programmed. One can be converted by program into a RPM setpoint alarm.
|
|
Contacts Capacity
Max. 130 Volts AC / DC, 2 amps AC or DC, 100 W. Overload protection required for inductive type loads.
|
|
Response to motion reverse
Signal goes into reverse direction after a programmable amount of pulses, or speed, in reverse direction. Forward direction will be signalized immediately. By program, the forward or reverse signal can also be assigned to no-motion condition.
|
|
Display
Speed by 5-digits readout, reverse direction by LED.
|
Speed/Difference Monitors
1, 2, or 3 available as optional addition, with their reference leg attached to A, B, or C. Speed measurement of own input, 5 digits, scaleable to RPM, measuring principle based on pulse interval with programmable minimum of time > 30 millisec. Digital comparison to the reference programmable, as difference, percentage difference, or ratio.. Own input with two paths of different level: Path to standard 3-leads sensors 7/6 volts, path to magnetic pick-ups > 50 mV RMS. Sensor supply (not monitored) 12 V / 60 mA.
|
|
Contact Output:
SPDT contact. Programmable to refer to either the own input speed measurement, or to one of the difference quantities.
|
|
Contact Capacity:
Max.130 Volts AC/DC, 2 amps AC or DC, 100 W. Overload protection required for inductive type loads.
|
|
Analog output:
Per program assigned to either the own input speed measurement, or to one of the difference quantities. 0/4-20 mA isolated circuit into max. 500 ohms load. Programmable span. Resolution 12 bit (1. 4096). Linearity error < 0.1 % of full scale.
|
|
Display:
5 digits, programmable to read the speed or one of the difference quantities.
|
Acceleration Monitor
Available as additional module in channel A, or in each A, B, C. Each provides 2 setpoint alarms, analog output, and display of the acceleration. Signal input internally tied to the corresponding channel input.
|
|
Measuring Principle:
The rotational speed, as the basis of determining the acceleration, is measured in the proven way of pulse distance extended over a minimum period of time. The acceleration then determines - according to its definition - from the difference between subsequent results and the time interval between them. Parameters are programmable to achieve stable and reliable measurements. The acceleration module does not participate in the test procedure.
|
|
Alarms:
SPNO contact, with programmable setpoint and response characteristics.
|
|
Analog output:
0/4-20 mA isolated circuit into max. 500 ohms load, with programmable span. Resolution 12 bit (1. 4096). Linearity error < 0.1 % of full scale.
|
|
Display:
4 digits and - sign for deceleration.
|
Dimension sheets available on request
Drehzahlüberwachung mit hoher Sicherheit
E16 - Systeme mit variablem Zuschnitt
passend zu allen Anforderungen und
gestuft für den geforderten Sicherheitsgrad:
Systeme E16x4 erfüllen API 670 und Stufe SIL2
Systeme E16x3 sind darüber hinaus zertifiziert für Stufe SIL3 nach IEC 61508,
uneingeschränkt und ohne weitere Auflagen für den Anwender.
E16 - Hauptteil
|
Herausragende Eigenschaften
Frequenzbereich 0 ... 30 kHz.
|
|
Struktur der Systeme
-
Jeder der 3 Kanäle enthält einen Monitor-Modul, steckbar im Systemrahmen. Jeder arbeitet unabhängig von den anderen und umfasst alle Funktionen vom Sensoreingang bis zu den Tripauslösekontakten durch Sicherheitsrelais. Sie sind durch Leiterbahnen auf der System-Rückplatte zur 2von3 Auswahl verdrahtet oder frei herausgeführt. Ausstattung des Monitors, Datenschnittstelle und weitere Funktionen nach Bedarf.
An keiner Stelle im System hängt die Sicherheit und Verfügbarkeit von nur 1 Element ab!
-
Unabhängig von den Kanälen kann übergeordnet ein Testgenerator vorgesehen werden, zur echten Funktionskontrolle der Kanäle im Betrieb. Prüfauslösung und Ergebnisprüfung manuell, oder automatisch in regelmäßigen Zyklen.
Bei Bedarf können - pro Kanal oder insgesamt -als Zusatzfunktionen hinzugefügt werden:
Trennstufen für eigensichere Sensoren im explosionsgefährdeten Bereich.
|
|
E16 - die Lösung zum Schutz von Mensch und Maschine, für höhere Verfügbarkeit der Anlage
und dadurch zum Nutzen des Anwenders.
|
|
Dieses flexible Konzept enthält Systeme mit allen denkbaren Sicherheits-Merkmalen. Durch die Wahl der Ausstattung an jede Anwendung kostengünstig anzupassen.
|
|
Ausstattungsgruppen der Systeme - ihre Eigenschaften und ihre Zulassung
Zwei Hauptgruppen: E16x3... undE16x4... unterscheiden sich durch ihre Ausstattung und Zulassung. Beide haben die 3-kanalige Gliederung mit gegenseitigem Vergleich und Ausfallerkennung, und die 2von3 Entscheidung. Voraussetzung und Kennzeichen für einen verlässlichen Drehzahlschutz, als Gewähr für die Auslösung im Gefahrfall, und zum Schutz gegen fälschliche Abschaltung. Die Ausstattung der Monitor-Module bestimmt die Sicherheit innerhalb jedes Kanals, und auch diesbezüglich sind alle E16-Systeme gleich. Ferner in der gebotenen Wahl der Bauform, der Stromversorgung und der Ausstattung mit zusätzlichen Funktionen.
Unterschiede liegen in der Intensität und im Ablauf der Selbstkontrolle, welche die Systeme beinhalten, und welche Testverfahren und Störmeldungen sie bieten. Danach richtet sich die Einfachheit der Handhabung für den Benutzer, und die Einordnung in die Zulassungs-Kategorie.
|
|
Die Systeme E16x3... erfüllen höchste Anforderungen, zugelassen für Sicherheitsstufe SIL3 nach IEC61508. Alle Systeme dieser Gruppe enthalten einen unabhängigen Test-Frequenzgenerator zur durchgängigen kanalweisen Auslöseprüfung. In der Ausstattung mit Testautomatik befreit dies den Anwender von der sonst vorgeschriebenen regelmäßigen Kontrolle mit Dokumentation und den damit verbundenen Kosten.
|
|
Die Systeme E16x4 sind geschaffen für Anwendungen, die den hohen Testkomfort nicht brauchen und die Kosten dafür nicht erlauben. Sie entsprechen aber den Vorschriften nach API 670 Sicherheitsklasse SIL2. Auch in dieser Gruppe ist eine Ausstattung mit Testfrequenzgenerator möglich und empfohlen.
Bezeichnungsschlüssel der Systeme und Zusätze:
|
|
|
Angaben für alle Systeme
Trip-Auslösung
Bei eingebauter 2von3 Auswahl sind die Sicherheitskontakte der Monitor im System schon auf der gedruckten Rückplatte verdrahtet zu zwei getrennten (unterbrechenden) Auslöse-Stromkreisen. Bei der Option mit getrennter Auslösung sind sie aus jedem Monitor (als Offner) einzeln auf den Ausgangsklemmen aufgelegt.
Die Angabe der Schaltleistung in der Monitorbeschreibung gilt auch für den Systemausgang.
Stromversorgung
Bei Speisung aus 3x24V DC sind die Anschlüsse für jeden Kanal getrennt auf Klemmen aufgelegt. Nullpunkt gemeinsam. Module, die keinem Kanal zugeordnet sind, werden aus einer systeminternen Sammelschiene versorgt.
Strombedarf (ohne Zusätze) ca. 3x 0,5 A.
Bei Speisung aus 2x115 V AC(100-130V) oder 2x230V AC (200 - 253V) AC versorgen zwei getrennt eingebaute Speisemodule eine System-Sammelschiene. Leistungsaufnahme ca. 60 VA.
Schutzklasse und Isolation 1.
|
|
Bauformen nach Wahl
(siehe Abbildungen und Maßzeichnungen)
-
Aufbaurahmen (A)
zum Aufsetzen z.B. auf eine Montageplatte im Innern eines Schaltschranks. Anschlussklemmen von vorn zugänglich.
Rahmen oben und unten offen, Schutzart IP 20.
Betriebsbedingungen
Umgebungstemperatur im Betrieb 0...+60 °C,
Lagertemperatur -40 °C... + 85 °C.
Feuchte max 95% (keine Betauung).
EMI und CE
nach 89/336/EWG, EN 61000-6-2, -6-4.
|

19-Zoll-Einschub
|
E16 - zur Sicherheit Ständige Sicherheits-Kontrollen in den Monitoren
Per Programm kann man jede dieser Kontrollen in die Sammel-Störmeldung des einzelnen Monitors einschließen. Damit lässt sich der Fehler frühzeitig beheben - schon wenn er auftritt.
Die Sicherheit der Auslösung im Gefahrfall bleibt bei Störung eines Monitors gewährleistet. Dafür sorgt die 2von3 Auswahl
|
|
Die 2von3 - Auswahl
Die drei Monitore arbeiten im System parallel und unabhängig. Jeder Monitor umfasst alles: Sensoreingang, Messung, Grenzwertvergleich. Am Ende steht das Sicherheitsrelais mit 2 Meldekontakten (Öffner). Erst wenn 2 von den 3 eine Überdrehzahl oder Störung melden, wird Trip ausgelöst. Eine einzelne abweichende Meldung von einem Monitor wird zwar erkannt, führt aber noch nicht zur Auslösung.
Bei eingebauter 2von3 Auswahl sind die beiden Kontakte der Sicherheitsrelais direkt auf der Rückplatte fest so verdrahtet. Es ist kein weiteres Element im Spiel. Am Ausgang des Systems stehen zwei isolierte Stromkreise zur Verfügung, die zur Trip-Auslösung gleichzeitig öffnen.
Bei getrennt herausgeführten Monitor-Meldungen muss die äußere Schaltung oder Hydraulik dies bewerkstelligen. Bei den E16x3 Systemen gibt es Rückmeldeeingänge hierfür, sodass die richtige Reaktion beim Test erkannt wird.
|
Ein einzelner Fehler kann nicht die Sicherheit der Auslösung gefährden, und er kann keine Fehlabschaltung herbeiführen. An keiner Stelle hängt die Sicherheit der Auslösung von einem einzelnen Element oder einer einzelnen Meldung ab.
|
|
E16 - Aufbau Version
|
Aufbau Rahmen von oben gesehen
|
|
|
Die 3 Monitore zur Drehzahl-Überwachung
Drehzahlmessung
Impulsabstandmessung mit automatisch gleitender Periodenzahl zur Sicherung einer Mindest-Messzeit von 5 Millisekunden.
Zusammenhang zwischen Sensor-Signalfrequenz und Drehzahl programmierbar, ebenso Dezimalstellen.
Genauigkeit ± 0,005 % ± 1 in der letzten der 5 Stellen.
Drehzahl-Grenzmeldungen
3 unabhängig einstellbare Grenzmeldungen:
Meldung SP1 ist für die Überdrehzahl vorgesehen, einstellbar in
Schaltpunkt, Hysterese-Breite und Schaltlage bei Überdrehzahl. Diese Meldung wirkt auf die Trip-Schaltung des Monitors, und zusätzlich auf die Monitor-Störmeldung (siehe unten).
Meldung SP2 dient der Plausibilitätskontrolle, der (einstellbare) Schaltpunkt darf bei laufender Maschine nicht unterschritten werden, sonst erkennt die Funktionsüberwachung eine offenbare Störung des Monitors.
Meldung SP3 ist frei verfügbar und dazu programmierbar nach Schaltpunkt, Breite und Lage der Hysterese, Schaltlage bei Unter/Überdrehzahl, bei Störmeldung und während der Anlaufüberbrückung. SP3 wirkt auf ein eigenes Melderelais (Schließer).
Anlaufüberbrückung setzt SP2 und SP3 in eine programmierbare Lage. Auslösung durch externen Kontakt oder Impuls, per Programm verlängerbar bis 999 s.
Tripausgang aus den Monitoren
Die beiden im Monitor vorhandenen Sicherheitsrelais werden auf stromlos gesteuert, sobald eine dieser Einzelmeldungen ansteht:
Schaltleistung der Trip-Meldekontakte (zugleich der nach außen geführten Trip-Auslösung):130 V AC/DC, max. 2 A, max. 100 W. Externe Funkenlöschung erforderlich.
Ein weiterer Kontakt aus den Sicherheitsrelais kann die Schaltlage an den Testgenerator-Modul zurückmelden. Dieser erkennt daraus bei Autotest-Ausstattung den korrekten Vollzug.
Sammel-Störmeldung
Wirkt als eine der Kriterien für den Trip-Ausgang des Monitors.
Per Programm kann jede der folgenden Überwachungen in die Sammelstörmeldung einbezogen oder davon ausgenommen werden:
Bei Sammel-Störmeldung unterbricht außerdem ein nach außen geführter Relaiskontakt.
Im Programm kann man festlegen, welche der Meldungen gespeichert werden, und welche sich selbst löschen, sobald die Störung behoben ist.
Eingang für das Sensorsignal
Ansprechpegel ausgelegt für unsere Sensoren der Reihe A5S oder ähnlich starke: >7/<3 Volt an 3 kΩ Eingangsimpedanz.
Optional für magnetinduktive Geber mit niedrigem Pegel, umschaltbar ca. 150/300 mV.
Eingang potenzialfrei, max. Spannung 60 V, Frequenzbereich bis 30 kHz.
Geberspeisung ca. 11 V/60mA kurzschlussfest.
Zur Prüfung des Monitors durch den Testgenerator wird der Eingang dorthin elektronisch umgeschaltet.
Anzeige
5-stellig für die Drehzahl-Messwerte, 8mm LED rot. Anstehende Störmeldungen werden als Code angezeigt. Während der Programmierphase Anzeige der Schritte und ihrer Parameter.
Statusanzeige durch farbige LED.
|
|
Datenschnittstelle
Nach RS232 oder wahlweise als PROFIBUS.
Ausgabe der Messwerte und anstehender Status- und Grenzmeldungen. Eingabe der Parameter des Monitors zusätzlich zu den Fronttasten.
Anschluss an frontseitiger Sub-D-Dose.
Weitergabe des Sensorsignals an andere Geräte
Gleichfrequent mit dem Sensorsignal (von der Prüfumschaltung aber nicht betroffen). Aktive Rechteckimpulse mit ca. 22 V bei 1kΩ Last. Ausgang potenzialfrei und ohne Rückwirkung auf den Monitor.
Analogausgänge (Option)
Wahlweise als Zusatzausstattung bis zu 3 Ausgänge (nicht bei PROFIBUS- Datenschnittstelle). Jeder Ausgang mit 20 mA in max 500Ω Last, getrennt programmierbar für Anfangs- und Endwert, mit/ohne live zero. Auflösung 12 bit, Linearitätsfehler <0,1%.
Steigende oder fallende Kennlinie ist programmierbar, ebenso das Verhalten bei erkannter Sensorstörung.
Der Testgenerator
Zur Prüfung der Reaktion im Gefahrfall kann den Kanälen im System ein Testgenerator übergeordnet werden. Ein wahlweiser Zusatz - aber zur Sicherheit empfohlen, und für die Systemausstattung nach IEC 61508 SIL 3 unerlässlich.
Testfrequenzen
Zur Reaktions-Kontrolle der Kanäle schaltet das System nacheinander auf die einzelnen Monitore statt der Sensoren eine Testfrequenz (= Testdrehzahl) auf. Sie wird vom unabhängigen Testgenerator bereitgestellt. Die jeweils aktive Test-Drehzahl wird im 5-stelligen Display des Testgenerators angezeigt, außerdem durch LED der geprüfte Kanal.
Für das Testverfahren selbst stehen zur Wahl:
Manueller Test
Durch frontseitige Tasten oder externe Einzel-Steuersignale
wird ein Kanal nach dem anderen auf Test umgeschaltet. Eine (abschaltbare) Verriegelung verhindert das Aufschalten von 2 Kanälen zugleich (was Tripauslösung zur Folge hätte). Die Testfrequenz selbst ist feinstufig durch Fronttasten durchstimmbar. Das Ansprechen lässt sich an Hand des Alarm-Status und die Fehlermeldung des Monitors beobachten.
Automatischer Test
Die Testautomatik schaltet nacheinander die Kanäle auf Test. In den einzelnen Prüfschritten werden Prüffrequenzen auf den Kanal aufgeschaltet, oberhalb und unterhalb der Auslösedrehzahl. Man legt sie im Programm gemäß Anwendung fest. Sie werden im Programm festgelegt. Die richtige Reaktion der Monitore prüft die Testautomatik anhand der Rückmeldung aus deren Sicherheitsrelais. Bei einer falschen Reaktion erfolgt selbsttätig eine System-Störmeldung (durch Kontakt). Die Automatik verhindert einen fälschlichen Trip nach erkanntem Fehler. Die Zeitabstände zwischen den Testphasen sind programmierbar.
Bei der Ausstattung nach IEC 61508 SIL 3 prüft der Testgenerator den korrekten Ablauf mehrfach selbst nochmals, und betätigt abhängig davon einen eigenen Fehlermeldekontakt.
Diese automatische Testroutine ersetzt die sonst vorgeschriebenen regelmäßigen manuellen Kontrollarbeiten: Zeitersparnis und höhere Verfügbarkeit der Anlage.
Weitere Mess- und Überwachungsfunktionen
Dazu können Zusatzmodule in das System integriert werden. Sie nutzen die ohne schon fehlergesicherten Signaleingänge des Hauptteils. In die Testvorgänge sind sie nicht einbezogen. Die Zusätze können einzelnen Kanälen zugeordnet werden, oder allen drei. Dann kann man die Aussagekraft für diese Funktion durch eine 2von3 Meldungsauswahl (als Zusatzmodul) noch erhöhen.
Beschreibungen im Anschluss an die Funktionsdiagramme.
|
Diagramm des E16-Hauptteils
Ausführung zusätzlicher Funktionen nach Wahl
Beispiele als Diagramm
|
1 Die wählbaren Zusatzausstattungen
Zusätzliche Drehzahl-Grenzmeldungen
Für die Automatisierung beim Hochlauf oder Stillsetzen können pro Kanal 4 oder 8 Schaltpunkte hinzugefügt werden, je mit eigenem Ansprechverhalten, mit eigenem Relaiskontakt (Schließer).
Drehrichtungs-Meldung
Besonders zur Überwachung von Pumpen und Drehwerken. Dieser Zusatz braucht einen speziellen Sensor (Reihe A5S3...). Dieser kann aber auch für das Hauptsystem genutzt und überwacht werden. Ausgang als Relaiskontakt-Wechsler. Eigener Analogausgang möglich. Datenschnittstelle nur nach RS232.
Beschleunigungsmeldung
Modul mit selbständigem Drehzahl-Messteil auf Impulsabstand-Prinzip mit einstellbarer Mindestmesszeit. Beschleunigung gebildet aus der Differenz aufeinander folgender Drehzahlmessungen. Anzahl der dabei einbezogenen Messvorgänge programmierbar.
Maßeinheit nach Wahl U/min/sec oder U/min/min.
Meldung mit zwei einstellbaren Schaltpunkten über Relaiskontakt-Schließer. 4-stellige Anzeige mit -Vorzeichen. RS232 Schnittstelle und Analogausgang als wahlweiser Zusatz.
|
|
Drehzahl anderer Antriebe und ihre Differenz
zur Hauptmaschine
Typisch die Anwendung beim Drehwerk der Turbine, für die Freigabe des Kupplungsvorgangs bei Gleichlauf. Der zusätzlich erfasste Antrieb benutzt naturgemäß einen eigenen Drehzahlsensor mit eigenem Systemeingang. Dieser Modul besitzt zwei digitale Messteile, die unabhängig von der Überwachung der Turbine arbeiten. Aus ihren Messwerten bildet der Zusatzmodul digital die Differenz bzw. das Verhältnis und steuert damit eigenen Anzeige, Analogausgang und eigene Grenzmelder an.
Zusätzliche Messmodule mit Profibus-Schnittstelle
Jeder Modul misst selbständig die Drehzahl des Hauptantriebs. Dies kann auch allein als eigenständiges System mit 3 Kanälen ausgeführt werden. Die Profibus Ausgänge stehen zur Meldung an andere Geräte zur Verfügung, beispielsweise für die schnell folgende Ausgabe der Istdrehzahl an einen Regler.
Trennstufen zu eigensicheren Sensoren im Ex-Bereich
Im Aufschnappgehäuse für Tragschiene außerhalb des E16-Systems. Alle Sensoren der Baureihen A5S1.. sind anschließbar. Auch deren Sensorstromkreis wird mit überwacht.
Ausführliche Angaben unter D461 im Abschnitt „Einbaugeräte".
|
|