Application Characteristics
-
Specifically preferred within automotive and motor testing installations, with paper and textile machines for monitoring stretch and shrinkage, and with flow systems to determine the ratio between streams.
- For applications within hazardous areas we recommend our versions with Ex-proof enclosure, series D124Ex9.
Measuring Principle 2 measuring channels, M and B, operate in parallel. Both use the advantageous frequency measuring principle, distinguished by pulse distance evaluation, automatically extended over a programmable period of time. The ideal combination of tracking speed and average, as appropriate for the application. The unit precisely regards the relationship between the process quantity (speed) and the transmitted frequency, by digital (scaling), individually for both channels. Thus, any required reading can be established. Measuring accuracy ± 0.01 % ± 1 in last significant digit. Minimum time extension for every measuring period programmable 30 millisec up to 10 seconds. Composite Quantities With the measured results from both channels M and B, the unit continuously computes their ratio, difference, and sum. Thereby, a total of 6 different quantities is held at the user's disposal: Variable M Variable B Ratio M ÷ B Difference M - B Sum M + B Percentage difference (M - B) ÷ B. Any one of them may individually be assigned to analog conversion, to (jointly both) setpoint alarms and to display. Sensor Signal Inputs Both channels M and B provide two input paths, accepting all our sensors. Both are isolated from power supply, and have common zero. The high level path responds with on/off >7/<4 volts. Max. signal 150 v. Impedance 100 k. Frequency 0-100 kHz. The high sensitivity path responds to > 50 millivoltsRMS, max 35 v DC may be superimposed. Max. signal 100 v. Impedance 50 k. Frequency 1-50 kHz. Sensor supply:
12 volts/60 ma (common to both channels),
and 2x8 volts via 1k for 2leads NAMUR types.
|
|
Analog Output
Isolated circuit, convertible to full scale 20 ma (max load 500 Ω) or 10 volts (max load 3 ma). Live zero programmable. Assigned alternatively by program to any one of the 6 listed quantities. Resolution 12 bit (1: 4096). Linearity error < 0.1 % of full scale. Tracking delay = measuring period. Setpoint Alarms 2 alarms with SPDT relay contacts. Assigned (jointly) per program to any of the 6 listed quantities. Response characteristics individually programmable: setpoint, hysteresis bandwidth and location, condition at no power and during starter period. Response delay approx. 5 millisec + measuring period. Each handling max 250 v/2 amp AC resp. 100 watts DC under overload protection. Display 5 digit (resp. 4 digit and minus sign), with bright red figures. Versions C and D have 14 mm height, version E uses 8 mm. Decimals and blank zeroes can be programmed. The display update sequence may be increased beyond the minimum measuring period for easier readability. During the programming phase, the display reads the step number and its corresponding parameter. HOLD function An external control signal, if active, holds the display at the most recent measurement. But it does not freeze the measurement nor the outputs. MAX/MIN memory Maximum and minimum measurements are memorized to be re- called to the display by keys. Another key initiates a new memorizing period, cancelling previous values. Data Interface (Option) RS232 (for PROFIBUS see version 124.1S4). Transmitting measurements subsequent to demand. No configuration of parameters via Interface.
Power Supply Options
18...40 volts AC/DC (suffix U1 to model No) 85..265 volts AC/DC (suffix U2 to model No)
Power consumption approx 5 VA.
Operating Conditions
Ambient temperature 0°C ... +50 °C (30 ...95 °F)
Optionally, the snap-on-track version (D) is available with extended temperature range -25 ... + 65 °C (suffix M to model No).
Humidity max 70%, without condensation.
Insulation Category I
Compatibility to Standards
EMI according to EN 610000-6.2, EN 610000..-6.4,
Safety according to EN 61010-1
|